Eltek Flatpack S

Description

Eltek Flatpack S DC-power system. Template for 2 rectifiers, 1 battery set. No solar power. No wind. No generator. Version 0.3 - Kari Karvonen kari.karvonen@kasenet.fi Eltek mibs available ftp://ftp.eltek.com. Ask your dealer or support for username and pass.

Overview

Basic monitoring template for Eltek Flatpack / SmartPack S. 48VDC power system. 2 inverters. One batttery set. No solar power. No generator.

Template is for Zabbix 4.4.0rc1

Items

Power System Company
Power System Site
Power System Model
Power System Serial Number
Rectifiers Temperature Value
Rectifier 1 Input Voltage
Rectifier 2 Input Voltage
Rectifier 1 Output Current Value
Rectifier 2 Output Current Value
Rectifier 1 Status
Rectifier 2 Status
Battery 1 Status
Battery 1 Temperature Value
Battery 1 Total Capacity Value
Battery 1 Voltage Value
Battery 1 Remaining Capacity Value
Battery 1 Current Value
Main Control Unit Temperature Value
Mains Outage Total
Mains Voltage Status L1
Mains Voltage Status L2
Mains Voltage Value L1
Mains Voltage Value L2

Triggers

Lost mains power L1
Lost mains power L2
Battery high temperature
Battery low temperature
Battery 1 low remaining capacity

Author

Kari Karvonen

Macros used

Name Description Default Type
{$BATTERY_CAPACITY_LOW_CRITICAL}

Amper hours capacity left before alarm

5 Text macro
{$BATTERY_TEMP_HIGH_CRITICAL}

-

40 Text macro
{$BATTERY_TEMP_HIGH_WARNING}

-

25 Text macro
{$BATTERY_TEMP_LOW_CRITICAL}

-

-20 Text macro
{$BATTERY_TEMP_LOW_WARNING}

-

0 Text macro
{$SNMP_COMMUNITY}

SNMPv2 read only community

public Text macro

Template links

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
Rectifier 2 Output Current Value

-

SNMP agent rectifierOutputCurrentValue.2

Update: 1m

Battery 1 Temperature Value

-

SNMP agent batteryTemperaturesValue.0

Update: 1m

Battery 1 Voltage Value

-

SNMP agent batteryVoltageValue.0

Update: 1m

Rectifier 2 Status

error (0) normal (1) minorAlarm (2) majorAlarm (3) disabled (4) disconnected (5) notPresent (6) minorAndMajor (7) majorLow (8) minorLow (9) majorHigh (10) minorHigh (11) event (12) valueVolt (13) valueAmp (14) valueTemp (15) valueUnit (16) valuePerCent (17) critical (18) warning (19)

SNMP agent rectifierStatus.2

Update: 1m

Battery 1 Status

error (0) normal (1) minorAlarm (2) majorAlarm (3) disabled (4) disconnected (5) notPresent (6) minorAndMajor (7) majorLow (8) minorLow (9) majorHigh (10) minorHigh (11) event (12) valueVolt (13) valueAmp (14) valueTemp (15) valueUnit (16) valuePerCent (17) critical (18) warning (19)

SNMP agent batteryStatus.0

Update: 1m

Mains Voltage Status L2

error (0) normal (1) minorAlarm (2) majorAlarm (3) disabled (4) disconnected (5) notPresent (6) minorAndMajor (7) majorLow (8) minorLow (9) majorHigh (10) minorHigh (11) event (12) valueVolt (13) valueAmp (14) valueTemp (15) valueUnit (16) valuePerCent (17) critical (18) warning (19)

SNMP agent mainsVoltageStatus.2

Update: 1m

Load Current Value

-

SNMP agent loadCurrentValue.0

Update: 1m

Mains Voltage Value L1

-

SNMP agent mainsVoltageValue.1

Update: 1m

Main Control Unit Temperature Value

-

SNMP agent mainControlUnitTemperatureValue

Update: 1m

Rectifier 1 Input Voltage

-

SNMP agent rectifierInputVoltageValue.1

Update: 1m

Load 1 Voltage Value

-

SNMP agent loadVoltageValue.1

Update: 1m

Power System Model

-

SNMP agent powerSystemModel.0

Update: 1h

Battery 1 Current Value

-

SNMP agent batteryCurrentsValue.0

Update: 1m

Load Status

-

SNMP agent loadStatus.0

Update: 1m

Rectifier 2 Input Voltage

-

SNMP agent rectifierInputVoltageValue.2

Update: 1m

Mains Outage Total

-

SNMP agent mainsOutageTotal.0

Update: 1m

Power System Site

-

SNMP agent powerSystemSite.0

Update: 1h

Power System Serial Number

-

SNMP agent powerSystemSerialNumber.0

Update: 1h

Rectifier 1 Status

error (0) normal (1) minorAlarm (2) majorAlarm (3) disabled (4) disconnected (5) notPresent (6) minorAndMajor (7) majorLow (8) minorLow (9) majorHigh (10) minorHigh (11) event (12) valueVolt (13) valueAmp (14) valueTemp (15) valueUnit (16) valuePerCent (17) critical (18) warning (19)

SNMP agent rectifierStatus.1

Update: 1m

Rectifiers Temperature Value

-

SNMP agent rectifiersTemperatureValue.0

Update: 1m

Battery 1 Total Capacity Value

-

SNMP agent batteryTotalCapacityValue.0

Update: 1h

Battery 1 Remaining Capacity Value

-

SNMP agent batteryRemainingCapacityValue.0

Update: 1m

Output power

-

Calculated LoadOutputPower.0

Update: 1m

Mains Voltage Value L2

-

SNMP agent mainsVoltageValue.2

Update: 1m

Power System Company

-

SNMP agent powerSystemCompany.0

Update: 1h

Mains Status

-

SNMP agent mainsStatus.0

Update: 1m

Power System Status

-

SNMP agent powerSystemStatus.0

Update: 1m

Mains Voltage Status L1

error (0) normal (1) minorAlarm (2) majorAlarm (3) disabled (4) disconnected (5) notPresent (6) minorAndMajor (7) majorLow (8) minorLow (9) majorHigh (10) minorHigh (11) event (12) valueVolt (13) valueAmp (14) valueTemp (15) valueUnit (16) valuePerCent (17) critical (18) warning (19)

SNMP agent mainsVoltageStatus.1

Update: 1m

Rectifier 1 Output Current Value

-

SNMP agent rectifierOutputCurrentValue.1

Update: 1m

Triggers

There are no triggers in this template.